Water Plant Statistics

Plant Statistics
Public Water System ID 310683
Resident Population Served 1600 persons/day
Non-Resident Population Served 3000 persons/day
Total Population Served
4600 persons/day


Plant Data
Water Source Groundwater
Depth of Wells 70 - 90 feet
Water Treatment Plant Design & Capacity 1 Million Gallons per Day or 700 gallons per minute
Plant Type Neptune Aquarius Microfloc package plant
Plant Process Aeration, Flocculation, Coagulation, Sedimentation, Filtration, Disinfection
Post Treatment 10 - 40 Cu. Ft. Activated Carbon Canisters in dry standby
Reservoir 1,500,000 gallons above ground storage tank
Disinfection
Mixed Oxidants - (MIOX Corporation)


Raw Water Quality
Temperature 33 - 36 degrees F
Benzene 22 - 30 ug/l or ppb
Iron 14 - 17 mg/l
Manganese .6 - .7 mg/l
Silica 30 mg/l
Hardness 280 - 320 mg/l as CaCO3
pH 7.3 - 7.6


Finished Water Quality
Temperature 50 - 56 degrees F.
Iron 0.01 mg/l
Manganese 0.0 mg/l
Silica 30 mg/l
Hardness 280 - 300 mg/l as CaCO3
pH 7.3 - 7.6
Turbidity .07 - .09 NTU (Nephelometric Turbidity Units)
Free Chlorine Residual 0.35 - 0.66 mg/l (on Campus)
Fluoride 0.19 mg/l (naturally occurring)
Benzene less than 0.002 ppb or ug/l (below detection limit)
TTHM 44 ug/l or ppb
Lead .005 mg/l (action limit = 0.015 mg/l)
Copper .508 mg/l (action limit = 1.3 mg/l)
Nitrate 1.93 mg/l MCL = 10 mg/l
Other Treatment Problems Crenothrix (Bacterial Iron - a nuisance bacteria, not harmful)
Hydrogen Sulfide (H2S)
Definitions
  • mg/l = Milligrams per liter, same as parts per million (ppm)
  • ug/l = Micrograms per liter, also expressed as parts per billion (ppb)
  • MCL = Maximum contaminant level is the highest level of a contaminant allowed in drinking water
  • TTHM = Total Trihalomethanes
  • NTU = Nephelometric Turbidity Units is a standard measurement of cloudiness in water, more sensitive than even the human eye can see. We monitor turbidity because it is a good indicator of the effectiveness of our water filtration system. High turbidity can hinder the effectiveness of disinfectants
Back to Top